mPower 311 Series
Models 311-62 • 1.5 kW
2U • 208–240 1ph Vac 50/60 Hz 1
DC Voltage | DC Current | Part No. | 240 Vac Amps 2 Duty Rating (Breaker Minimum) |
220 Vac Amps 2 Duty Rating (Breaker Minimum) |
208 Vac Amps 2 Duty Rating (Breaker Minimum) |
120 Vac Amps 1,2 Duty Rating (Breaker Minimum) |
60 V | 60 A | MPW 311-62-0060-060-004 | 7.61 • (9.51) | 8.30 • (10.38) | 8.78 • (10.98) | 12.83 • (16.03) |
80 V | 60 A | MPW 311-62-0080-060-004 | 7.61 • (9.51) | 8.30 • (10.38) | 8.78 • (10.98) | 12.83 • (16.03) |
200 V | 25 A | MPW 311-62-0200-025-004 | 7.57 • (9.46) | 8.26 • (10.32) | 8.74 • (10.92) | 12.69 • (15.86) |
360 V | 15 A | MPW 311-62-0360-015-004 | 7.57 • (9.46) | 8.26 • (10.32) | 8.74 • (10.92) | 12.69 • (15.86) |
500 V | 10 A | MPW 311-62-0500-010-004 | 7.53 • (9.41) | 8.22 • (10.27) | 8.69 • (10.86) | 12.56 • (15.70) |
750 V | 6 A | MPW 311-62-0750-006-004 | 7.53 • (9.41) | 8.22 • (10.27) | 8.69 • (10.86) | 12.56 • (15.70) |
[1] Requires 208-240 Vac to reach full 1.5 kW power output. Optionally, 120 Vac can be used with a derated 1.2 kW power output.
[2] Duty Rating is calculated with: ((Watts * 102%) / Efficiency%) / (Vac – 10%) / PowerFactor. Breaker Rating is calculated with: (Duty Amps / 80%). The Breaker Rating is a minimum requirement. Choose the equivalent or next higher standard breaker rating. The AC wiring must be rated for at least the same current as the breaker. Wire per local codes.
Models 311-62 • 3 kW
2U • 208–240 1ph Vac 50/60 Hz 3
DC Voltage | DC Current | Part No. | 240 Vac Amps 4 Duty Rating (Breaker Minimum) |
220 Vac Amps 4 Duty Rating (Breaker Minimum) |
208 Vac Amps 4 Duty Rating (Breaker Minimum) |
120 Vac Amps 3,4 Duty Rating (Breaker Minimum) |
60 V | 120 A | MPW 311-62-0060-120-004 | 15.22 • (19.03) | 16.61 • (20.76) | 17.57 • (21.96) | 16.03 • (20.04) |
80 V | 120 A | MPW 311-62-0080-120-004 | 15.22 • (19.03) | 16.61 • (20.76) | 17.57 • (21.96) | 16.03 • (20.04) |
200 V | 50 A | MPW 311-62-0200-050-004 | 15.14 • (18.93) | 16.52 • (20.65) | 17.47 • (21.84) | 15.86 • (19.83) |
360 V | 30 A | MPW 311-62-0360-030-004 | 15.14 • (18.93) | 16.52 • (20.65) | 17.47 • (21.84) | 15.86 • (19.83) |
500 V | 20 A | MPW 311-62-0500-020-004 | 15.06 • (18.83) | 16.43 • (20.54) | 17.38 • (21.73) | 15.70 • (19.62) |
750 V | 12 A | MPW 311-62-0750-012-004 | 15.06 • (18.83) | 16.43 • (20.54) | 17.38 • (21.73) | 15.70 • (19.62) |
1000 V | 10 A | MPW 311-62-1000-010-004 | 15.06 • (18.83) | 16.43 • (20.54) | 17.38 • (21.73) | 15.70 • (19.62) |
1500 V | 6 A | MPW 311-62-1500-006-004 | 15.06 • (18.83) | 16.43 • (20.54) | 17.38 • (21.73) | 15.70 • (19.62) |
[3] Requires 208-240 Vac to reach full 3.0 kW power output. Optionally, 120 Vac can be used with a derated 1.5 kW power output.
[4] Duty Rating is calculated with: ((Watts * 102%) / Efficiency%) / (Vac – 10%) / PowerFactor. Breaker Rating is calculated with: (Duty Amps / 80%). The Breaker Rating is a minimum requirement. Choose the equivalent or next higher standard breaker rating. The AC wiring must be rated for at least the same current as the breaker. Wire per local codes.
Models 311-33 • 5 kW
3U • 380–480 1ph Vac 50/60 Hz 5
DC Voltage | DC Current | Part No. | 480 Vac Amps 6 Duty Rating (Breaker Minimum) |
208 Vac Amps 5,6 Duty Rating (Breaker Minimum) |
60 V | 170 A | MPW 311-33-0060-170-004 | 12.62 • (15.77) | 17.47 • (21.84) |
80 V | 170 A | MPW 311-33-0080-170-004 | 12.62 • (15.77) | 17.47 • (21.84) |
200 V | 70 A | MPW 311-33-0200-070-004 | 12.62 • (15.77) | 17.47 • (21.84) |
360 V | 40 A | MPW 311-33-0360-040-004 | 12.55 • (15.69) | 17.29 • (21.61) |
500 V | 30 A | MPW 311-33-0500-030-004 | 12.55 • (15.69) | 17.29 • (21.61) |
750 V | 20 A | MPW 311-33-0750-020-004 | 12.55 • (15.69) | 17.29 • (21.61) |
[5] Requires 380-480 Vac 1 phase to reach full 5 kW power output. Optionally, 208 Vac 1 phase can be used with a derated 3 kW power output.
[6] Duty Rating is calculated with: ((Watts * 102%) / Efficiency%) / (Vac – 10%) / PowerFactor. Breaker Rating is calculated with: (Duty Amps / 80%). The Breaker Rating is a minimum requirement. Choose the equivalent or next higher standard breaker rating. The AC wiring must be rated for at least the same current as the breaker. Wire per local codes.
Models 311-53 • 10 kW
3U • 380–480 3ph Vac 50/60 Hz 7
DC Voltage | DC Current | Part No. | 480 Vac Amps 8 Duty Rating (Breaker Minimum) |
208 Vac Amps 7,8 Duty Rating (Breaker Minimum) |
60 V | 340 A | MPW 311-53-0060-340-004 | 14.59 • (18.24) | 20.20 • (25.25) |
80 V | 340 A | MPW 311-53-0080-340-004 | 14.59 • (18.24) | 20.20 • (25.25) |
200 V | 140 A | MPW 311-53-0200-140-004 | 14.59 • (18.24) | 20.20 • (25.25) |
360 V | 80 A | MPW 311-53-0360-080-004 | 14.44 • (18.04) | 19.99 • (24.98) |
500 V | 60 A | MPW 311-53-0500-060-004 | 14.44 • (18.04) | 19.99 • (24.98) |
750 V | 40 A | MPW 311-53-0750-040-004 | 14.44 • (18.04) | 19.99 • (24.98) |
1000 V | 30 A | MPW 311-53-1000-030-004 | 14.44 • (18.04) | 19.99 • (24.98) |
1500 V | 20 A | MPW 311-53-1500-020-004 | 14.44 • (18.04) | 19.99 • (24.98) |
[7] Requires 380-480 Vac 3 phase to reach full 10 kW power output. Optionally, 208 Vac 3 phase can be used with a derated 6 kW power output.
[8] Duty Rating is calculated with: ((Watts * 102%) / Efficiency%) / (Vac – 10%) / PowerFactor / 1.73. Breaker Rating is calculated with: (Duty Amps / 80%). The Breaker Rating is a minimum requirement per line. Choose the equivalent or next higher standard breaker rating. The AC wiring must be rated for at least the same current as the breaker. Wire per local codes.
Models 311-53 • 15 kW
3U • 380–480 3ph Vac 50/60 Hz 9
DC Voltage | DC Current | Part No. | 480 Vac Amps 10 Duty Rating (Breaker Minimum) |
208 Vac Amps 9,10 Duty Rating (Breaker Minimum) |
60 V | 510 A | MPW 311-53-0060-510-004 | 21.88 • (27.35) | 30.30 • (37.87) |
80 V | 510 A | MPW 311-53-0080-510-004 | 21.88 • (27.35) | 30.30 • (37.87) |
200 V | 210 A | MPW 311-53-0200-210-004 | 21.88 • (27.35) | 30.30 • (37.87) |
360 V | 120 A | MPW 311-53-0360-120-004 | 21.65 • (27.07) | 29.98 • (37.48) |
500 V | 90 A | MPW 311-53-0500-090-004 | 21.65 • (27.07) | 29.98 • (37.48) |
750 V | 60 A | MPW 311-53-0750-060-004 | 21.65 • (27.07) | 29.98 • (37.48) |
1000 V | 40 A | MPW 311-53-1000-040-004 | 21.65 • (27.07) | 29.98 • (37.48) |
1500 V | 30 A | MPW 311-53-1500-030-004 | 21.65 • (27.07) | 29.98 • (37.48) |
2000 V | 20 A | MPW 311-53-2000-020-004 | 21.65 • (27.07) | 29.98 • (37.48) |
[9] Requires 380-480 Vac 3 phase to reach full 15 kW power output. Optionally, 208 Vac 3 phase can be used with a derated 9 kW power output.
[10] Duty Rating is calculated with: ((Watts * 102%) / Efficiency%) / (Vac – 10%) / PowerFactor / 1.73. Breaker Rating is calculated with: (Duty Amps / 80%). The Breaker Rating is a minimum requirement per line. Choose the equivalent or next higher standard breaker rating. The AC wiring must be rated for at least the same current as the breaker. Wire per local codes.
Models 311-54 • 30.0 kW
4U • 380–480 3ph Vac 50/60 Hz 11
DC Voltage | DC Current | Part No. | 480 Vac Amps 12 Duty Rating (Breaker Minimum) |
208 Vac Amps 11,12 Duty Rating (Breaker Minimum) |
60 V | 1000 A | MPW 311-54-0060-1000-004 | 43.49 • (54.36) | 60.22 • (75.27) |
80 V | 1000 A | MPW 311-54-0080-1000-004 | 43.49 • (54.36) | 60.22 • (75.27) |
200 V | 420 A | MPW 311-54-0200-420-004 | 43.40 • (54.25) | 60.09 • (75.11) |
360 V | 240 A | MPW 311-54-0360-240-004 | 43.17 • (53.96) | 59.78 • (74.72) |
500 V | 180 A | MPW 311-54-0500-180-004 | 42.86 • (53.57) | 59.34 • (74.18) |
750 V | 120 A | MPW 311-54-0750-120-004 | 42.86 • (53.57) | 59.34 • (74.18) |
920 V | 125 A | MPW 311-54-0920-125-004 | 42.86 • (53.57) | 59.34 • (74.18) |
1000 V | 80 A | MPW 311-54-1000-080-004 | 43.17 • (53.96) | 59.78 • (74.72) |
1500 V | 60 A | MPW 311-54-1500-060-004 | 42.86 • (53.57) | 59.34 • (74.18) |
2000 V | 40 A | MPW 311-54-2000-040-004 | 42.86 • (53.57) | 59.34 • (74.18) |
[11] Requires 380-480 Vac 3 phase to reach full 30 kW power output. Optionally, 208 Vac 3 phase can be used with a derated 18 kW power output.
[12] Duty Rating is calculated with: ((Watts * 102%) / Efficiency%) / (Vac – 10%) / PowerFactor / 1.73. Breaker Rating is calculated with: (Duty Amps / 80%). The Breaker Rating is a minimum requirement per line. Choose the equivalent or next higher standard breaker rating. The AC wiring must be rated for at least the same current as the breaker. Wire per local codes.