Optima™ PDUs
Product SelectorMPD 520078-000 
1U PDU Specs
    
    Legacy Product
This product is available for purchase, but may take longer than a similar standard catalog part number.
		Power Outlets
	
	Front Panel
			(2) 5-20R, 120V 
		Rear Panel
			(2) 5-20R, 120V 
(8) 5-20R, 120V (S)
		(8) 5-20R, 120V (S)
Other Panels
			None
		
		Power Input 
	
	Voltage
			120 Vac
		Phase
			Single Phase
		Frequency
			50/60 Hz
		Max Current
			30 Amps
		Max Load
			2.88 KVA
		Connection
			L5-30P, 9 ft cord, 3-wire 10 ga, SJT jacket (Rear panel)
		Voltage Monitor
			None
		Current Monitor
			None
		
		Power Protection
	
	Spike/Surge
			Yes
		EMI Filter
			Yes
		Over Current
			(2) 20A Circuit Breaker
		
		Remote, Interlocks, and Environment Sensors
	
	Local EPO
			None
		Remote EPO Type
			N.O./N.O.  (view Commander UCP panels)
		Interlocks
			0
		Temperature
			0
		Humidity
			0
		
		Communications and Interfaces
	
	Display
			None
		Serial
			None
		Ethernet
			None
		Protocols
			None
		
		Physical
	
	Layout
			1U
		Dimensions
			1U x 19" W x 9" D
		Materials
			Chassis: Steel
		Finishes
			Chassis: Zinc plated Black
FrontPanel: Zinc plated Black
		FrontPanel: Zinc plated Black
		Operating Conditions
	
	Temperature
			32° to 122° Fahrenheit
		Humidity
			5% to 85% Relative Humidity
		Elevation
			6,562 feet
		
		Conformance
	
	Warranty
			See warranty page for details
		Conformances
			UL
		Notes:
Read the product Feature Descriptions for important details. Specifications are subject to change without notice.
[1] Certain details of the circuitry may only be revealed by the schematic (available separately).
[2] All ratings of amps are maximum. See model details for deratings.
[3] Feature codes: Enet = Ethernet, VMtr = volts meter, AMtr = amps meter, rEPO = remote EPO, Seq = outlet sequencing, EMI = EMI filter, Srg = surge suppression
[4] Outlet Codes: (S) = switched, (V) = monitored voltage, (A) = monitored amps. Check Feature Descriptions for details.
