Optima™ PDUs
Product SelectorMPD 411408
3U PDU Specs
Power Outlets
Front Panel
(2) C13, 230V
Rear Panel
(4) 6-20R, 230V (S)
(2) C13, 230V
(4) C13, 230V (S)
(2) C13, 230V
(4) C13, 230V (S)
Other Panels
None


Power Input
Voltage
230 Vac
Phase
Single Phase
Frequency
50/60 Hz
Max Current
50 Amps
Max Load
9.20 KVA
Connection
6-50P, 15 ft cord, 5-wire 6 ga, SOOW jacket (Rear panel)
Voltage Monitor
None
Current Monitor
None
Power Protection
Spike/Surge
Yes
EMI Filter
Yes
Over Current
(1) 50A Main Breaker
(2) 20A Circuit Breaker
(4) 10A Circuit Breaker
(2) 20A Circuit Breaker
(4) 10A Circuit Breaker
Remote, Interlocks, and Environment Sensors
Local EPO
None
Remote EPO Type
N.O./None (view Commander UCP panels)
Interlocks
0
Temperature
0
Humidity
0
Communications and Interfaces
Display
None
Serial
None
Ethernet
None
Protocols
None
Physical
Layout
3U
Dimensions
3U x 19" W x 12" D
Materials
Chassis: Steel
Finishes
Chassis: Zinc plated Gold
FrontPanel: Painted Gray
FrontPanel: Painted Gray
Operating Conditions
Temperature
32° to 122° Fahrenheit
Humidity
5% to 85% Relative Humidity
Elevation
6,562 feet
Conformance
Warranty
See warranty page for details
Conformances
no specific certifications
Notes:
Read the product Feature Descriptions for important details. Specifications are subject to change without notice.
[1] Certain details of the circuitry may only be revealed by the schematic (available separately).
[2] All ratings of amps are maximum. See model details for deratings.
[3] Feature codes: Enet = Ethernet, VMtr = volts meter, AMtr = amps meter, rEPO = remote EPO, Seq = outlet sequencing, EMI = EMI filter, Srg = surge suppression
[4] Outlet Codes: (S) = switched, (V) = monitored voltage, (A) = monitored amps. Check Feature Descriptions for details.